Tacikistan: 50 Hz; MV 35/10/6 kV; HV 500/220/110 kV; IEC 60076, GOST 11677, Barki Tojik Standards, CASA-1000.

Tacikistan Elektrik & Şebeke Mühendislik Profili

Tacikistan: 50 Hz; MV 35/10/6 kV; HV 500/220/110 kV; IEC 60076, GOST 11677, Barki Tojik Standards, CASA-1000.

Tacikistan Elektrik & Şebeke Mühendislik Profili

Tacikistan

Grid frequency
50 Hz
Distribution voltages
35, 10, 6 kV
Transmission voltages
500, 220, 110 kV
Low-voltage levels
400, 230 V
MV Lightning Impulse Withstand (BIL)
170 kVp
MV Power Frequency Withstand (1 min)
70 kV RMS
Typical MV Fault Rating
20 kA RMS
MV Neutral Grounding Regime
isolated
Specific Creepage Distance
20 mm/kV
Design Seismic Acceleration (PGA)
0.25 g
Energy Efficiency Regulation
IEC 60076 Loss Guidelines / National Grid Code