Taikai 50 MVA 110/34.5 kV On-Load Tap-Changing (OLTC) Step-Down Power Transformer | Taikai Transformer (Taikai Group) - VOLTFORMER

Taikai Transformer (Taikai Group) 50 MVA 110/34.5 kV. No-Load Loss (P0): 23500W, Load Loss (Pk): 168000W, Impedance (Uk): %10.5. Taikai 50 MVA 110/34.5 kV On-Lo

Taikai 50 MVA 110/34.5 kV On-Load Tap-Changing (OLTC) Step-Down Power Transformer

Taikai 50 MVA 110/34.5 kV On-Load Tap-Changing (OLTC) Step-Down Power Transformer belongs to the Substation Step-Down Power Transformers (110-330 kV) category and is rated at 50 MVA with 110/34.5 kV primary/secondary voltage. Application: 110 kV Urban & Industrial Zone Step-Down Substations. Final ratings must be verified against the manufacturer datasheet.

Taikai 50 MVA 110/34.5 kV On-Load Tap-Changing (OLTC) Step-Down Power Transformer

Taikai Transformer (Taikai Group)

Rated Power
50 MVA
Primary Voltage
110 kV
Secondary Voltage
34.5 kV
No-Load Loss (P0)
23.5 kW
Load Loss (Pk)
168.0 kW
Short-Circuit Impedance (Uk)
%10.5
Winding Material
Copper (Cu-Cu)
Cooling Type
ONAN/ONAF
Loss Class
State Grid High Efficiency Standard
Vector Group
YNd11
Total Weight
66000 kg
Standards & Certification
IEC 60076, IEEE C57, TS EN 60076

https://www.taikaitransformer.com/