Schneider Electric 3150 kVA 34.5/0.8 kV Solar PV Step-Up Transformers | Schneider Electric - VOLTFORMER

Schneider Electric 3,150 kVA 34.5/0.8 kV. No-Load Loss (P0): 2020W, Load Loss (Pk): 23100W, Impedance (Uk): %6.5. Schneider Electric Minera MP 3150 kVA syntheti

Schneider Electric 3150 kVA 34.5/0.8 kV Solar PV Step-Up Transformers

Schneider Electric Minera MP 3150 kVA synthetic ester liquid fire-safe solar step-up transformer.

Schneider Electric 3150 kVA 34.5/0.8 kV Solar PV Step-Up Transformers

Schneider Electric

Rated Power
3,150 kVA
Primary Voltage
34.5 kV
Secondary Voltage
0.8 kV
No-Load Loss (P0)
2.02 kW
Load Loss (Pk)
23.1 kW
Short-Circuit Impedance (Uk)
%6.5
Winding Material
Copper (Cu-Cu)
Cooling Type
KNAN
Loss Class
Ecodesign Tier 2
Vector Group
Dy11y11
Total Weight
8100 kg
Standards & Certification
IEC 60076-16 (Solar PV standard), TS EN 50708 series, EU 548/2014 + 2019/1783 Tier 2, IEEE C57.159

https://www.se.com/ww/en/product-range/1070-minera-mp/

https://www.se.com/ww/en/