Haihong 50 MVA 110/35 kV 3D Three-Dimensional Triangular Wound-Core Power Transformer | Haihong Electric (Guangdong Haihong) - VOLTFORMER
Haihong Electric (Guangdong Haihong) 50 MVA 110/35 kV. No-Load Loss (P0): 18500W, Load Loss (Pk): 165000W, Impedance (Uk): %10.5. Haihong 50 MVA 110/35 kV 3D Th
Haihong 50 MVA 110/35 kV 3D Three-Dimensional Triangular Wound-Core Power Transformer
Haihong 50 MVA 110/35 kV 3D Three-Dimensional Triangular Wound-Core Power Transformer belongs to the Substation Step-Down Power Transformers (110-330 kV) category and is rated at 50 MVA with 110/35 kV primary/secondary voltage. Application: 110 kV Regional Grid Step-Down Substations. Final ratings must be verified against the manufacturer datasheet.
Haihong 50 MVA 110/35 kV 3D Three-Dimensional Triangular Wound-Core Power Transformer
Haihong Electric (Guangdong Haihong)
- Rated Power
- 50 MVA
- Primary Voltage
- 110 kV
- Secondary Voltage
- 35 kV
- No-Load Loss (P0)
- 18.5 kW
- Load Loss (Pk)
- 165.0 kW
- Short-Circuit Impedance (Uk)
- %10.5
- Winding Material
- Copper (Cu-Cu)
- Cooling Type
- ONAN/ONAF
- Loss Class
- 3D Triangular Wound Core Ultra-Low Loss
- Vector Group
- YNd11
- Total Weight
- 62000 kg
- Standards & Certification
- IEC 60076, IEEE C57, TS EN 60076