GE Vernova Mining-Duty 2500 kVA 13.8/0.48 kV Transformer | GE Vernova (General Electric) - VOLTFORMER

GE Vernova (General Electric) 2,500 kVA 13.8/0.48 kV. No-Load Loss (P0): 3700W, Load Loss (Pk): 23600W, Impedance (Uk): %4.5. GE Vernova mining-duty distributio

GE Vernova Mining-Duty 2500 kVA 13.8/0.48 kV Transformer

GE Vernova mining-duty distribution transformer family for medium-voltage extraction and processing loads.

GE Vernova Mining-Duty 2500 kVA 13.8/0.48 kV Transformer

GE Vernova (General Electric)

Rated Power
2,500 kVA
Primary Voltage
13.8 kV
Secondary Voltage
0.48 kV
No-Load Loss (P0)
3.70 kW
Load Loss (Pk)
23.6 kW
Short-Circuit Impedance (Uk)
%4.5
Winding Material
Copper (Cu-Cu)
Cooling Type
ONAN
Loss Class
Configuration-specific loss class
Vector Group
Dyn11
Total Weight
6200 kg
Standards & Certification
IEC 60079-0 / 60079-1 (explosive atmosphere Ex-d), IEC 60076-11, ATEX

https://www.gevernova.com/electrification/equipment/transformers/distribution-transformers

https://www.gevernova.com/grid-solutions/sites/default/files/resources/products/brochures/distribution_transformers/prolecmining.pdf

https://www.gevernova.com/electrification/automation/protection-control-metering/