Eaton Cooper Power 3750 kVA 34.5/0.48 kV Dead-Front Loop-Feed Pad-Mounted Transformer | Eaton / Cooper Power - VOLTFORMER

Eaton / Cooper Power 3,750 kVA 34.5/0.48 kV. No-Load Loss (P0): 2800W, Load Loss (Pk): 27500W, Impedance (Uk): %6.2. Eaton Cooper Power 3750 kVA 34.5 kV dead-fr

Eaton Cooper Power 3750 kVA 34.5/0.48 kV Dead-Front Loop-Feed Pad-Mounted Transformer

Eaton Cooper Power 3750 kVA 34.5 kV dead-front loop-feed compartmental pad-mounted transformer.

Eaton Cooper Power 3750 kVA 34.5/0.48 kV Dead-Front Loop-Feed Pad-Mounted Transformer

Eaton / Cooper Power

Rated Power
3,750 kVA
Primary Voltage
34.5 kV
Secondary Voltage
0.48 kV
No-Load Loss (P0)
2.80 kW
Load Loss (Pk)
27.5 kW
Short-Circuit Impedance (Uk)
%6.2
Winding Material
Aluminum (Al-Al)
Cooling Type
KNAN
Loss Class
Ecodesign Tier 2
Vector Group
Dyn1
Total Weight
8900 kg
Standards & Certification
IEEE C57.12.26 / C57.12.34, IEC 60076, ANSI C57

https://www.eaton.com/us/en-us/catalog/transformers/three-phase-pad-mounted-compartmental-type-transformer.html

https://www.eaton.com/