BEST Transformer 250 MVA 380/154/34.5 kV Three-Winding Interconnection Autotransformer | BEST Trafo (Balıkesir Elektromekanik) - VOLTFORMER
BEST Trafo (Balıkesir Elektromekanik) 250 MVA 380/154 kV. No-Load Loss (P0): 68000W, Load Loss (Pk): 360000W, Impedance (Uk): %12.5. BEST Transformer 250 MVA 38
BEST Transformer 250 MVA 380/154/34.5 kV Three-Winding Interconnection Autotransformer
BEST Transformer 250 MVA 380/154/34.5 kV Three-Winding Interconnection Autotransformer belongs to the Interconnection & Transmission Autotransformers (345-380 kV) category and is rated at 250 MVA with 380/154 kV primary/secondary voltage. Application: TEİAŞ 380 kV National Grid Backbone Main Interconnection Substation. Final ratings must be verified against the manufacturer datasheet.
BEST Transformer 250 MVA 380/154/34.5 kV Three-Winding Interconnection Autotransformer
BEST Trafo (Balıkesir Elektromekanik)
- Rated Power
- 250 MVA
- Primary Voltage
- 380 kV
- Secondary Voltage
- 154 kV
- No-Load Loss (P0)
- 68.0 kW
- Load Loss (Pk)
- 360.0 kW
- Short-Circuit Impedance (Uk)
- %12.5
- Winding Material
- Copper (Cu-Cu)
- Cooling Type
- ONAN/ONAF/OFAF
- Loss Class
- TEİAŞ 380 kV Transmission Standard
- Vector Group
- YNa0d11
- Total Weight
- 185000 kg
- Standards & Certification
- TEİAŞ technical specification, IEC 60076, TS EN 60076