ABB 2000 kVA 34.5/0.4 kV Loop-Feed Underground Distribution Pad-Mounted Transformer | ABB / Hitachi Energy - VOLTFORMER
ABB / Hitachi Energy 2,000 kVA 34.5/0.4 kV. No-Load Loss (P0): 1450W, Load Loss (Pk): 16000W, Impedance (Uk): %6. ABB 2000 kVA 34.5 kV loop-feed pad-mounted out
ABB 2000 kVA 34.5/0.4 kV Loop-Feed Underground Distribution Pad-Mounted Transformer
ABB 2000 kVA 34.5 kV loop-feed pad-mounted outdoor distribution transformer with dead-front safety construction.
ABB 2000 kVA 34.5/0.4 kV Loop-Feed Underground Distribution Pad-Mounted Transformer
ABB / Hitachi Energy
- Rated Power
- 2,000 kVA
- Primary Voltage
- 34.5 kV
- Secondary Voltage
- 0.4 kV
- No-Load Loss (P0)
- 1.45 kW
- Load Loss (Pk)
- 16.0 kW
- Short-Circuit Impedance (Uk)
- %6
- Winding Material
- Copper (Cu-Cu)
- Cooling Type
- ONAN
- Loss Class
- Ecodesign Tier 2
- Vector Group
- Dyn11
- Total Weight
- 5800 kg
- Standards & Certification
- IEEE C57.12.26 / C57.12.34, IEC 60076, ANSI C57
https://www.hitachienergy.com/products-and-solutions/transformers