Toshiba Energy Systems 250 MVA 275/66 kV Substation Step-Down Power Transformers (110-330 kV) - Substation Step-Down Power Transformers (110-330 kV), номинальная мощность 250 MVA, первичное/вторичное напряжение 275/66 kV. Применение: 275 kV Metropolitan and Regional Transmission Substations. Окончательные параметры необходимо подтвердить по паспорту производителя.

Toshiba Energy Systems 250 MVA 275/66 kV Substation Step-Down Power Transformers (110-330 kV)

Toshiba Energy Systems

Potenza nominale
250 MVA
Tensione primaria
275 kV
Tensione secondaria
66 kV
Perdite a vuoto (P0)
68.0 kW
Perdite sotto carico (Pk)
480.0 kW
Impedenza di cortocircuito (Uk)
%13.5
Materiale degli avvolgimenti
Copper (Cu-Cu)
Tipo di raffreddamento
ONAN/ONAF
Classe di perdita
IEC / JEC SOTA
Gruppo vettoriale
YNd11
Peso totale
195000 kg
Norme e certificazioni
IEC 60076, IEEE C57, JEC