Siemens Energy GEAFOL® 1000 kVA 34.5/0.4 kV Transformador seco en resina | Siemens Energy - VOLTFORMER
Siemens Energy 1,000 kVA 34.5/0.4 kV. Perdite a vuoto P₀: 1350W, Perdite sotto carico Pₖ: 8800W, Impedenza: %6. Siemens Energy GEAFOL® 1000 kVA 34.5/0.4 kV Tran
Siemens Energy GEAFOL® 1000 kVA 34.5/0.4 kV Transformador seco en resina
Siemens Energy GEAFOL® 1000 kVA 34.5/0.4 kV Transformador seco en resina - Cast-Resin Dry-Type Transformers, номинальная мощность 1000 kVA, первичное/вторичное напряжение 34.5/0.4 kV. Применение: Indoor, Shopping Malls, Hospitals & Airports. Окончательные параметры необходимо подтвердить по паспорту производителя.
Siemens Energy GEAFOL® 1000 kVA 34.5/0.4 kV Transformador seco en resina
Siemens Energy
- Potenza nominale
- 1,000 kVA
- Tensione primaria
- 34.5 kV
- Tensione secondaria
- 0.4 kV
- Perdite a vuoto (P0)
- 1.35 kW
- Perdite sotto carico (Pk)
- 8.8 kW
- Impedenza di cortocircuito (Uk)
- %6
- Materiale degli avvolgimenti
- Copper (Cu-Cu)
- Tipo di raffreddamento
- AN/AF
- Classe di perdita
- Ecodesign Tier 2
- Gruppo vettoriale
- Dyn11
- Peso totale
- 3800 kg
- Norme e certificazioni
- IEC 60076-11, DIN EN 50588, EU 548/2014 + 2019/1783 Tier 2
https://www.siemensenergy.com/global/en/home/products-services/product-offerings/transformers.html