Mitsubishi Electric 500 MVA 500/22 kV Generator Step-Up Transformers (GSU) | Mitsubishi Electric - VOLTFORMER
Mitsubishi Electric 500 MVA 500/22 kV. Perdite a vuoto P₀: 110000W, Perdite sotto carico Pₖ: 850000W, Impedenza: %16. Mitsubishi Electric 500 MVA 500/22 kV Gene
Mitsubishi Electric 500 MVA 500/22 kV Generator Step-Up Transformers (GSU)
Mitsubishi Electric 500 MVA 500/22 kV Generator Step-Up Transformers (GSU) - Generator Step-Up Transformers (GSU), номинальная мощность 500 MVA, первичное/вторичное напряжение 500/22 kV. Применение: 500 kV Grid Connection Points for Large Power Plants. Окончательные параметры необходимо подтвердить по паспорту производителя.
Mitsubishi Electric 500 MVA 500/22 kV Generator Step-Up Transformers (GSU)
Mitsubishi Electric
- Potenza nominale
- 500 MVA
- Tensione primaria
- 500 kV
- Tensione secondaria
- 22 kV
- Perdite a vuoto (P0)
- 110.0 kW
- Perdite sotto carico (Pk)
- 850.0 kW
- Impedenza di cortocircuito (Uk)
- %16
- Materiale degli avvolgimenti
- Copper (Cu-Cu)
- Tipo di raffreddamento
- ODAF
- Classe di perdita
- JEC / IEC SOTA GSU
- Gruppo vettoriale
- YNd11
- Peso totale
- 320000 kg
- Norme e certificazioni
- IEC 60076, IEEE C57, JEC
https://www.mitsubishielectric.com/eig/energysystems/products/transmission/