Surinam Perfil de ingeniería eléctrica y de red | VOLTFORMER
Surinam: 60 Hz; MV 33/12.6/6.3 kV; HV 161/69 kV; IEC 60076, EBS Standards, NEN Standards.
Surinam Perfil de ingeniería eléctrica y de red
Surinam: 60 Hz; MV 33/12.6/6.3 kV; HV 161/69 kV; IEC 60076, EBS Standards, NEN Standards.
Surinam Perfil de ingeniería eléctrica y de red
Surinam
- Grid frequency
- 60 Hz
- Distribution voltages
- 33, 12.6, 6.3 kV
- Transmission voltages
- 161, 69 kV
- Low-voltage levels
- 400, 230, 220, 127 V
- MV Lightning Impulse Withstand (BIL)
- 125 kVp
- MV Power Frequency Withstand (1 min)
- 50 kV RMS
- Typical MV Fault Rating
- 16 kA RMS
- MV Neutral Grounding Regime
- low-resistance
- Specific Creepage Distance
- 25 mm/kV
- Design Seismic Acceleration (PGA)
- 0.05 g
- Energy Efficiency Regulation
- IEC 60076 / EBS Standards