Madagascar Perfil de ingeniería eléctrica y de red | VOLTFORMER

Madagascar: 50 Hz; MV 20/10/5.5 kV; HV 138/63/35 kV; IEC 60076, JIRAMA Specifications.

Madagascar Perfil de ingeniería eléctrica y de red

Madagascar: 50 Hz; MV 20/10/5.5 kV; HV 138/63/35 kV; IEC 60076, JIRAMA Specifications.

Madagascar Perfil de ingeniería eléctrica y de red

Madagascar

Grid frequency
50 Hz
Distribution voltages
20, 10, 5.5 kV
Transmission voltages
138, 63, 35 kV
Low-voltage levels
400, 230 V
MV Lightning Impulse Withstand (BIL)
125 kVp
MV Power Frequency Withstand (1 min)
50 kV RMS
Typical MV Fault Rating
16 kA RMS
MV Neutral Grounding Regime
low-resistance
Specific Creepage Distance
31 mm/kV
Design Seismic Acceleration (PGA)
0.1 g
Energy Efficiency Regulation
IEC 60076 / JIRAMA Standards