Australia
- Grid frequency
- 50 Hz
- Distribution voltages
- 33, 22, 11, 6.6 kV
- Transmission voltages
- 500, 330, 275, 220, 132, 66 kV
- Low-voltage levels
- 415, 240 V
- MV Lightning Impulse Withstand (BIL)
- 170 kVp
- MV Power Frequency Withstand (1 min)
- 70 kV RMS
- Typical MV Fault Rating
- 25 kA RMS
- MV Neutral Grounding Regime
- low-resistance
- Specific Creepage Distance
- 25 mm/kV
- Design Seismic Acceleration (PGA)
- 0.08 g
- Energy Efficiency Regulation
- AS/NZS 60076.10:2024 / GEMS MEPS