# Teksan TJ1000PE

> diesel-generator-set - 1006 kVA standby / 915 kVA prime Perkins 4008TAG1A motorlu dizel jeneratör seti; TJ-509-T MK3 kontrolör, 85 dB(A) @ 7 m kanopi.

**Voltformer canonical:** https://voltformer.com/product/teksan-tj1000pe - markdown version: https://voltformer.com/product/teksan-tj1000pe.md

## Overview

- **Brand:** Teksan
- **Product family:** TJ Series
- **Application:** 1006 kVA standby / 915 kVA prime Perkins 4008TAG1A motorlu dizel jeneratör seti; TJ-509-T MK3 kontrolör, 85 dB(A) @ 7 m kanopi.
- **Product type:** diesel-generator-set

## Power Ratings (ISO 8528)

| Rating | kVA | kW |
|---|---|---|
| Prime power (PRP) | 915 | 732 |
| Standby power (LTP/ESP) | 1006 | 804 |

- **Voltage / frequency:** 400/230 V, 50 Hz, 3-phase, 0.8 PF
- **Rated current:** 1452 A
- **Fuel consumption @ 75% load:** 142 L/h

## Engine & Alternator

- **Engine:** Perkins 4008TAG1A (8-cylinder in-line, 30.561 L, Turbocharged, air-to-air aftercooled, 1500 rpm)
- **Governing:** ISO 8528-5
- **Alternator:** Brushless - Class H-F, IP23
- **Controller:** TJ-509-T MK3

## Mechanical & Acoustic

- **Enclosure:** Soundproof canopy
- **Dimensions (L×W×H):** 5820 × 2200 × 2435 mm
- **Weight:** 9830 kg - **Fuel tank:** 1650 L
- **Noise @ 7 m:** 85 dB(A)

## Standards

- ISO 8528
- ISO 3046
- BS 5514
- DIN 6271
- IEC 60034-1
- 2000/14/EC

## Sources

- https://www.teksan.com/en/diesel-generator-TJ1000PE-400-1/

- **Source scope:** manufacturer-family
- **Last reviewed:** 2026-09-13

Manufacturer portfolio/family source. Confirm the exact order code, guaranteed ratings and project-specific options against the current OEM datasheet before procurement or an SLD study.

Ratings follow the manufacturer datasheet ISO 8528 definitions. Site-specific fuel, exhaust, cooling and paralleling engineering require qualified verification before procurement.