# Schneider Electric PowerLogic PM5560

> energy-meter - Panel-mounted multifunction power meter for electrical distribution monitoring, energy metering and power-quality observation.

**Voltformer canonical:** https://voltformer.com/product/schneider-electric-powerlogic-pm5560-energy-meter - markdown version: https://voltformer.com/product/schneider-electric-powerlogic-pm5560-energy-meter.md

## Overview

- **Brand:** Schneider Electric
- **Product family:** PowerLogic PM5000 power meters
- **Category:** Grid Equipment & Power Quality / instrument-transformers-and-metering

## Manufacturer-stated technical envelope

- **System voltage:** ≤ 690 V L-L / 400 V L-N
- **CT input:** 1 / 5 A
- **Frequency:** 45–65 Hz
- **Active-energy accuracy:** Class 0.2S at 5 A; Class 0.5S at 1 A (IEC 62053-22)
- **Reactive-energy accuracy:** Class 2 (IEC 62053-23)
- **Harmonic measurement:** through order 63
- **Communications:** Modbus RS-485; Modbus TCP/IP; EtherNet/IP; BACnet
- **Measured quantities:** Current; Voltage; Frequency; Power factor; Active and reactive power; Energy
- **Mounting:** 96 × 96 mm panel mount

## Standards

- IEC 61557-12
- IEC 62053-22 Class 0.2S
- IEC 62053-23 Class 2
- IEC/UL 61010-1

## Official sources

- https://www.se.com/us/en/product/METSEPM5560/power-meter-powerlogic-pm5560-2-ethernet-up-to-63th-harmonic-11mb-4di-2do-52-alarms/
- https://download.se.com/files?p_Doc_Ref=GDE41422&p_File_Name=GDE41422-05.pdf&p_enDocType=Instruction+sheet

- **Source scope:** manufacturer-family
- **Last reviewed:** 2026-09-13

Manufacturer portfolio/family source. Confirm the exact order code, guaranteed ratings and project-specific options against the current OEM datasheet before procurement or an SLD study.

The stated values are family or catalogue-option limits. Select the exact order code and verify project-specific duties before procurement or release of an SLD design.