  "title": "Instrument Transformers: CT and VT Selection for Metering and Protection",
  "summary": "A CT/VT specification guide covering ratio, accuracy class, burden, knee-point voltage, transient performance, insulation level and IEC 61869 digital secondary interfaces.",
  "readTime": "8 min read",
  "date": "2026-09-06",
  "author": "Voltformer Measurement & Protection Engineering",
  "category": "Instrument Transformers & Metering",
  "tags": [
    "Current Transformer",
    "Voltage Transformer",
    "IEC 61869",
    "Burden VA",
    "Knee-Point Voltage"
  ],
  "contentMarkdown": "### 1. Measurement and Protection Are Different CT Jobs\n\nIEC 61869-1:2023 applies to newly manufactured instrument transformers for measurement, protection and control, including analogue and digital secondary signals. A metering core is selected for accuracy around normal load; a protection core is selected to remain useful during high fault current and transient conditions. Combining both duties in one unspecified core creates avoidable saturation and billing errors.\n\n### 2. Core Selection Matrix\n\nSpecify the certified class and burden range for the actual core. Protection parameters depend on that class and application: an accuracy-limit factor, transient data and knee-point data are not interchangeable requirements for every core. Add the external device and wiring impedances on the same secondary-current and frequency basis. Complex impedances must be summed before taking their magnitude; a sum of VA magnitudes is only a screening approximation when power factors are unknown. CT winding resistance is separate from external burden, although excitation and protection-performance calculations may need it.\n\nFor a dedicated equal outgoing/return copper pair, use the full loop resistance below. The length variable is explicitly one-way; shared returns, residual circuits and unequal conductors require the actual circuit model. The numerical inputs are assumptions at the stated resistivity, not manufacturer cable ratings. Both cable-only results exclude relay, terminals, test switches and CT internal resistance. Adjust conductor resistance for operating temperature and include every connected device. Nominal burden arithmetic does not establish transient saturation performance. See the complete [long-cable burden example](/articles/ct-secondary-1a-5a-long-cable-burden-calculation), [Schneider's burden guidance](https://www.se.com/ph/en/faqs/FA240104/) and [IEC inductive-CT scope](https://webstore.iec.ch/en/publication/6050).\n\n$$S_{external} = I_{sec}^2 |Z_{external}|, \\quad R_{loop} = 2\\rho L/A$$\n\n`L = 150 m; A = 2.5 mm²; ρ = 0.0175 Ω·mm²/m; R_loop = 2.10 Ω`\n\n`1 A → 2.10 VA; 5 A → 52.50 VA`\n\n### 3. VT, Digital Output and Insulation Coordination\n\nVoltage transformers require ratio, accuracy, burden, ferroresonance behaviour, earthing arrangement and the correct phase-to-earth or phase-to-phase insulation level. Where a process bus is used, IEC 61869-9 and IEC 61850 engineering replace analogue copper assumptions with a defined digital interface, time source, merging-unit performance and network redundancy.\n\n### 4. Factory and Site Verification\n\n- Confirm the highest voltage for equipment, power-frequency withstand and lightning impulse withstand.\n- Check short-time thermal current, dynamic current, secondary terminal safety and earthing.\n- Measure ratio, polarity, winding resistance, insulation and excitation; document the complete protection loop burden.\n- Never copy a CT class from a relay datasheet without calculating the installed cable loop and fault duty.\n\n*Reference: IEC 61869-1:2023; IEC 61869-2:2012; IEC 61869-3; IEC 61869-9.*",
  "contentLanguage": "en",
  "sources": [
    {
      "name": "Schneider Electric — external CT burden and cable resistance",
      "url": "https://www.se.com/ph/en/faqs/FA240104/"
    },
    {
      "name": "IEC 61869-2:2012 — public scope",
      "url": "https://webstore.iec.ch/en/publication/6050"
    }
  ]
}