1. Physics of Partial Discharge in Solid Dielectrics

Partial discharge (PD) is a localized electrical breakdown within micro-voids, delaminations, or cast impurities in the solid epoxy resin matrix. Under high electric field gradient, electron avalanches gradually erode the surrounding insulation.

2. Routine Factory Acceptance Criteria (IEC 60076-11)

Per IEC 60076-11, dry-type transformers must undergo mandatory PD measurement via coupling capacitor circuits calibrated per IEC 60270:

1. Pre-Stress Voltage: Voltage is ramped to 1.8 × Um / √(3) and held for 30 seconds to initiate any potential PD activity.

2. Measurement Voltage: Voltage is decreased to 1.3 × Um / √(3) and held for 3 minutes while measuring apparent charge.

3. Acceptance Threshold:

q ≤ 10 pC

3. Phase-Resolved Partial Discharge (PRPD) Pattern Diagnostics

Defect TypePRPD Phase Distribution PatternRoot Cause Mechanism
Internal Gas Cavity / VoidDischarges centered around 45° and 225° with equal positive/negative polarityTrapped micro-bubbles during vacuum resin casting
Surface TrackingDischarges centered around voltage zero-crossings (0° and 180°)Surface dust, moisture, or resin contamination
Corona into AirSharp discharge cluster at the negative peak (270°)Sharp metallic burr or unshielded connection point

4. Field Diagnostics & Inception Voltage (PDIV)

In field commissioning, ensuring that the Partial Discharge Inception Voltage (PDIV) is at least 1.30 × higher than nominal system voltage guarantees zero degradation over 30+ years of operation.

*Reference: IEC 60270:2000+AMD1:2015; IEC 60076-11:2018; CIGRE TB 676.*